enwitec grid and plant protection – 86.3 kVA – according to VDE-AR-N 4105:2018-11 – 10018565

Info

Network and plant protection (NA) from enwitec. Depending on the national directive, generating plants must be shut down in the event of impermissible voltage or frequency deviations in the low-voltage grid. If the limit values permissible in the application rule are exceeded, the generation plant is automatically disconnected from the grid. If the mains voltage or mains frequency is back in the permissible range, the system is automatically switched on again. We offer both standard products and individual solutions, which are adapted to the needs of the respective photovoltaic system.

This network and system protection is specially built for the German and Austrian market, in accordance with VDE-AR-N 4105:2018-11 and ÖVE TOR R25 NS ASYNC .

Note
Match code: NA-Schutz-PV-86.3KVA-NH-TNS_TT

Technical data

Item no.: 10018565
Mains type: TT / TN-S
Power: 86.3 kVA
Country approval: VDE-AR-N 4105:2018-11 and ÖVE TOR R25 NS ASYNC
Separation: all-pole
test disconnect terminal block: yes
Inputs: 1x
mains input terminals: 16 – 95 mm²
Outputs: 3 x NH 000
Output terminals: 2.5 – 35 mm²
Cable entries: Cable grommet M63 / glands